air source heat pump Error code and solution

Good quality Air source heat pump for sales
Good quality Air source heat pump for sales
I'm Online Chat Now
Company News
air source heat pump Error code and solution

Code

Description

How to solve

01E

Wrong phase

Change phase

02E

Lack Phase

Check power supply wire

03E

Water flow switch

Check water flow or flow switch wire connecting, if switch damaged, change it

04E

Antifreeze

 

05E

High pressure

Water flow is too small

06E

Low pressure

No refrigerant or leaked

07E

High pressure 2

Water flow is too small

08E

Low pressure 2

No refrigerant or leaked

09E

Communication

Check if the communication line between PC board and operating panel connects firmly

11E

Time limited

Cancel the preset working time

12E

High Exhaust temp

Refer to 4.2

13E

High Exhaust temp 2

Refer to 4.2

15E

Tank temp sensor damage

Change tank temp sensor

16E

Copper Coil temp sensor damage

Change the temp sensor below expansion valve

17E

Copper Coil temp sensor2 damage

Change the temp sensor below expansion valve 2

18E

Exhaust temp sensor

Change outlet gas temp sensor

(On the outlet pipe of compressor)

19E

Exhaust temp sensor 2

Change outlet gas temp sensor 2

(On the outlet pipe of compressor 2)

21E

Air temp sensor

Change air temp sensor

22E

Return water temp sensor

Change return water temp sensor

23E

Over cold when cooling mode

Water flow is too small

25E

Water level switch damage

Change water level switch

27E

outlet Water temp sensor damage

Change Water outlet temp sensor

28E

outlet Water temp sensor2 damage

Change Water outlet temp sensor2

29E

Return gas temp sensor damage

Change return gas temp sensor

30E

Return gas temp sensor 2 damage

Change return gas temp sensor 2

31E

Water pressure switch damage

Check water pressure switch wire line

32 E

Outlet water temp too low when cooling

Check water pump or change setting temperature

35E

Compressor over current

Check if current and voltage stable

36E

Compressor 2 over current

Check if current and voltage stable

 